Webvision#

webVision authentication key may be defined in version 11.50.01. If it is defined then for webVision communication and global point transfer to work same key must be defined in both ends of communication.

Using this key is important security improvement to system.

If new version is upgraded to existing system and Fx must communicate with older Fx or with webVision older than 8.78.07 authentication key must be removed.

Each Fx should have unique key if they are in public internet (global point transfer does not work). This is good practice especially if dynamic IP addresses are used.